Part Number : 41 2 P10 LN2 10A | Manufacturer: Oakland Industries Ltd | NSN : 5925-01-323-0907 |
NIIN : 013230907 | Alternate P/N : 412P10LN210A | Item Name : circuit breaker |
CAGE Code : 06402 | FSC : 5925 Circuit Breakers | |
Part number 41 2 P10 LN2 10A with NSN 5925013230907, having item name Circuit Breaker, under FSC 5925 Circuit Breakers is available and ready for shipping. Sourced from Oakland Industries Ltd, you can easily order 41 2 P10 LN2 10A with CAGE Code 06402 at a competitive price. To get a quick quote for this part, fill out the form.
Please make sure to fill out the form as carefully and completely as possible. Pay extra attention to the asterisk (*) marked fields, as your response will determine the bulk of your quote. A representative will contact you within 15 of receiving your request.
NSN | FSC | NIIN | CLS | Hazmat | DEMIL | Cancelled NSN |
---|---|---|---|---|---|---|
5925-01-323-0907 Item Description: Circuit Breaker | 5925 | 013230907 | 0 | P | ||
CIIC | HCC | ESD | PMIC | Criticality | ENAC | |
U | A | 0 | ||||
Part Number | ISC | RNVC | RNCC | HCC | MSDS | SADC |
41 2 P10 LN2 10A | 5 | 2 | 5 |
MRC | Criteria | Characteristic |
---|---|---|
AAQL | BODY STYLE | SINGLE POLE TYPE |
ABXD | BUSHING LENGTH | 0.250 INCHES NOMINAL |
ADAQ | BODY LENGTH | 1.220 INCHES NOMINAL |
ADAT | BODY WIDTH | 0.710 INCHES NOMINAL |
ADTV | CASE MATERIAL | PLASTIC |
AEBP | CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO LENGTH | 0.780 INCHES NOMINAL |
AFJN | FRAGILITY FACTOR | MODERATELY RUGGED |
AJWX | MOUNTING SURFACE TO TERMINAL END DISTANCE | 1.130 INCHES MAXIMUM |
AKPX | POLE QUANTITY | 1 |
AXHR | MOUNTING FACILITY TYPE AND QUANTITY | 1 THREADED BUSHING |
BBRG | STORAGE TYPE | GENERAL PURPOSE WAREHOUSE |
CPLM | MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE | 10.0 AMPERES DC SINGLE LOCATION |
CPRF | OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS | 50.0 DC SINGLE LOCATION |
CPRG | MAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPS | 1000.0 DC SINGLE LOCATION |
CPRH | CIRCUIT PROTECTION TYPE | OVERCURRENT SINGLE LOCATION |
CPRL | TRIP RELEASE CHARACTERISTIC | TIME DELAY SINGLE LOCATION |
CPRW | ACTUATOR FUNCTION | TRIP-RESET |
CPRX | ACTUATOR POSITION DESIGNATION | AT POLE ONE |
CPSM | INTERNAL TRIP RELEASE CONFIGURATION | SERIES TRIP SINGLE LOCATION |
CQXF | INCLOSURE PROTECTION TYPE FOR WHICH DESIGNED | HUMIDITY RESISTANT AND VIBRATION RESISTANT |
CRCF | TRIP RELEASE AMBIENT TEMP RATING | 70.0 DEG FAHRENHEIT NOMINAL SINGLE LOCATION |
FEAT | SPECIAL FEATURES | UTILIZED ON GENERATOR SET,15KW TRAILER MTD,NSN6115013048184 |
THSD | THREAD SERIES DESIGNATOR | UNS |
TTQY | TERMINAL TYPE AND QUANTITY | 2 QUICK DISCONNECT, MALE |
CPRR | MAIN CONTACT TRIPPING MECHANISM TYPE | TRIP FREE |
CMLP | THREAD QUANTITY PER INCH | 32 |
CPRJ | TRIP RELEASE METHOD | THERMAL SINGLE LOCATION |
CPRN | ULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT | 140.0 SINGLE LOCATION |
CPRQ | RESET METHOD | MANUAL |
CPRT | MANUAL ACTUATOR TYPE AND QUANTITY | 1 PUSH BUTTON |
CQJX | NOMINAL THREAD SIZE | 0.375 INCHES |
CQWN | TRIP DELAY TIME IN SECONDS PER RATED CONTINUOUS CURRENT | 10.000 MINIMUM AT 200 PCT SINGLE LOCATION AND 40.000 MAXIMUM AT 200 PCT SINGLE LOCATION |
Warrantied inventory at competitive prices
Search the world's largest inventory of IT hardware, computer memory by manufacturer, category or part number
We sell only warrantied and traceable parts
All inventory ready to ship from our sellers
Don’t forget, If You Need a Quote for A Part, You Can Fill Out the Request for Quote form On the Homepage of This Website and Receive a Response Within Fifteen Minutes!